The GLINK allows access to the dataline for global programming, monitoring and control. The GLINK also provides a central time clocking function which automatically synchronizes/sets the clocks in all of the Lighting Automation Panels.
The GLINK is a desk mounted device with system monitoring capabilities and visual indication of:
The GLINK incorporates a built-in Ethernet Network card which is discoverable with supplied software. No need for comports!
No need for an additional Dataline Power Supply unit as the GLINK now has a built-in Dataline Power Supply.
Description: | Dataline Interface |
Catalog #: | GLINK |
Operating Environment: | 0-55 Degrees C (32-131 F) 0-95% RH, Non Condensing, Non Corrosive atmosphere. |
Weight: | 0.3 Kg / 0.5 lb. |
Alarm Contacts: | 2 Amp, 28 VAC Power |
Requirements: | 120 VAC outlet / 12 VDC Transformer (supplied) 120 VAC outlet / 24 VDC Transformer (supplied) |
This product is a technically advanced version of the RLINK.
The GCC48 is a plug-in controller card which is used in conjunction with 1-4 Relay Driver Cards. It provides the control logic and memory for operating a single Lighting Automation Panel with up to 48 relays and fourteen programmable switches. It also supports communications over its RS-232 port and the dataline. Address switches are rotary style with visual identification of the number set. Address can run from 000 to 999.
Description: | Lighting Automation Panel Controller Card |
Catalog #: | GCC48 |
Operating Environment: | 0-55 Degrees C (32-131°F) 0-95% RH, Non Condensing Non Corrosive atmosphere |
Weight: | 0.5 Kg /1 lb |
Codes: | UL 916 Energy Management
CSA Certified |
This product is a technically advanced version of the RCC48.
The GRDC12 is used in conjunction with the the GCC48 cards.
The GRDC12 actuates a bank of 12 relays ON and OFF and monitors their states.
It also monitors 3 programmable system switch inputs. Each card is associated with a bank of 12 relays. The 24 relay panel accepts two cards (1-12, 13-24), the 48 relay panel accepts four cards (1-12, 13-24, 25-36, 37-48).
Description: | 12 Relay Drive/Monitor Card |
Catalog #: | GRDC12 |
Operating Environment: | 0-55 Degrees C (32-131°F) 0-95% RH, Non Condensing Non Corrosive atmosphere |
Mounting: | In RINTER00xx |
Weight: | 0.5 Kg / 1 lb. |
Codes: | UL 916 Energy Management
CSA Certified |
This product is a technically advanced version of the RRDC12.
The GREPEAT is a dataline signal booster. It permits the total length of dataline to be extended beyond the normal 1219m (4,000’) limit. Use of a dataline repeater allows lighting control panels and dataline switches in large buildings, multi-office complexes, or distantly located sites to be networked together.
Each GREPEAT will extend the maximum dataline length by 1219m (4,000’). Other than the limit of 500 devices in any combination per dataline, there is no limit to the number of dataline repeaters that can be used together. The device supports longer data lines while reducing noise and providing protection against electrical transients
System communications through a GREPEAT are automatic. Status LED indicate proper operation and assist in diagnostics.
Description: | Dataline Repeater |
Catalog #: | GREPEAT |
Operating Environment: | 0-55 Degrees C (32-131°F) 0-95% RH, Non-Condensing Non-Corrosive atmosphere |
Power Requirements: | 24 VDC |
Dimensions: | 5.002” x 3.570” x 1.502” 127.05mm x 90.68mm x 38.15mm |
Weight: | 51g / 0.035 oz |
This product is a technically advanced version of the RREPEAT.
The GMISM is able to be used with almost any motion sensor that is on the market today, to control the GE relay.
The GMSIM has the ability to use the Blue Control wire or Auxillary Relay from any motion sensor to control a momentary input to the GE relay or circuit board.
The GMSIM also has connections for a momentary switch and Dry Contact for a BAS system.
Description: | Motion Sensor Interface Module |
Catalog #: | GMISM |
Operating Environment: | 0-55 Degrees C (32-131°F) 0-95% RH, Non Condensing Non Corrosive atmosphere |
Power Requirements: | 24 VDC |
Dimensions: | 5.002” x 3.570” x 1.502” 127.05mm x 90.68mm x 38.15mm |
Weight: | 51g / 0.035 oz |
The GPCON photo controller is a low- voltage class 2 device which provides three independent outputs that may be connected directly to relays or to an RMS. The control unit has adjustable switching ranges that allow adjustment for high and low setpoints of the deadband.
The control unit monitors daylighting of interiors, atriums, skylights and exterior lighting using one of four GLCS GPSEN-xxx photodiode sensing elements.
In normal operation, the controller has a 3 minute time delay to eliminate nuisance switching. The time delay may be bypassed for setup and testing. When the level of light increases to the adjustable high fc level and remains at or above that level for 3 minutes, a momentary closure between white and black will turn loads OFF. When the light level decreases below the adjustable Low level setpoint and remains at or below that level for 3 minutes, a momentary closure between white and red will turn loads ON
Description: | Photocell Controller |
Catalog #: | GPCON |
Weight: | .25 Kg/.5 lb. |
Operating Environment: | -18 to 45 Degrees C (0 - 113 F) 0-100% RH, Non Condensing Non Corrosive atmosphere |
Power Requirements: | 24 VAC |
Foot Candle Range: | User Selectable 0 - 10 10 - 100 100 - 1k 1k - 10k |
Time Delay: | 3 minutes Enable/Disable |
Mounting: | Mounts in any GMS ready control panel including GINTERxxxxRC, GBS-x, or GBRACKET-xx units. |
Codes: | UL 916 Energy Management CSA Certified |
This product is a technically advanced version of the RPCON.
GLC uses four different daylighting sensors to provide:
The sensors connect to the GPCON photocell control unit to provide photocell control.
Weight: | 0.12 Kg / 0.25 lb. |
Operating Environment: | -30° to 50° C (-20° to 120° F)
Weatherproof |
Power Requirements: | No external source required |
This product is a technically advanced version of the RPSEN-xxx.
Sensor | Style | Lens | Filter | Mounting | Orientation | Factory Set Max. Calibration |
GPSEN-IN | Indoor | Fresnel | Clear | Ceiling | Down | 100fc |
GPSEN-OUT | Outdoor | Flat | Clear | 1/2" NPT | Horizontal | 250fc |
GPSEN-ATR | Atrium | Dome | Opaque | 1/2" NPT | Horizontal | 1,000fc |
GPSEN-SKY | Skylight | Dome | Dark | 1/2" NPT | Up | 2,000fc |
These switches are designed for installation in mounting straps with covers or for snap in panel mounting [19mm (0.75)x33mm (1.3”)}. The line includes 2-button switches with normally open 3 AMP 28 VAC contacts providing a single-pole double-throw configuration. Each switch is provided with wire terminals 110mm (4.25”) 18AWG.
Description: | GLCS Series Switches |
Catalog #: | GS2-37 (Unlighted) |
Colour: | White Button with Black Trim |
Operating Environment: | 0-55 Degrees C (32-131°F) 0-95% RH, Non-Condensing Non-Corrosive atmosphere |
This product is a technically advanced version of the RS2-37.
These switches are designed for installation in mounting straps with covers or for snap in panel mounting [19mm (0.75)x33mm (1.3”)]. The line includes 2-button switches with normally open 3 AMP 28 VAC contacts providing a single-pole double-throw configuration.
The GS2-32P is a switch with a Pilot light with 0.04 AMP 28 VAC pilot lamp in “ON” button. Each switch is provided with wire terminals 110mm (4.25”) 18AWG.
Description: | GLCS Series Switches |
Catalog #: | GS2-37P (Pilot Light) |
Colour: | White Button with Black Trim |
Operating Environment: | 0-55 Degrees C (32-131°F) 0-95% RH, Non-Condensing Non-Corrosive atmosphere |
This product is a technically advanced version of the RS2-37P.
These switches are designed for installation in mounting straps with covers or for snap in panel mounting [19mm (0.75)x33mm (1.3”)}. The line includes 2-button switches with normally open 3 AMP 28 VAC contacts providing a single-pole double-throw configuration. Each switch is provided with wire terminals 110mm (4.25”) 18AWG.
Description: | GLCS Series Switches |
Catalog #: | GS2-32 (Unlighted) |
Colour: | Ivory Button with Black Trim |
Operating Environment: | 0-55 Degrees C (32-131°F) 0-95% RH, Non-Condensing Non-Corrosive atmosphere |
This product is a technically advanced version of the RS2-32.
These switches are designed for installation in mounting straps with covers or for snap in panel mounting [19mm (0.75)x33mm (1.3”)]. The line includes 2-button switches with normally open 3 AMP 28 VAC contacts providing a single-pole double-throw configuration.
The GS2-32P is a switch with a Pilot light with 0.04 AMP 28 VAC pilot lamp in “ON” button. Each switch is provided with wire terminals 110mm (4.25”) 18AWG.
Description: | GLCS Series Switches |
Catalog #: | GS2-32P (Pilot Light) |
Colour: | Ivory Button with Black Trim |
Operating Environment: | 0-55 Degrees C (32-131°F) 0-95% RH, Non-Condensing Non-Corrosive atmosphere |
This product is a technically advanced version of the RS2-32P.